PV management.
There is a special version of the RCS, the RCS-PV, for the management /
supervision of PV systems. The RCS-PV logs the PV system yield by counting
E-meter pulses. It calculates the momentary power of the PV system. The power is
displayed in the PC software as soon as there is a connection with an RCS-PV in
the field.
For the management of PV systems, the software has the following functions:
 |
calls RCS-PV units in the field automatically (i.e. each day, week) |
 |
reads out and stores the counter values |
 |
automatically generates reports of the measured values |
 |
automatically checks the performance of the system |
 |
automatically sends a fax or e-mail with the reports and/or error messages |
The RCS-PV and management software can be used cost-effectively for even very
small PV systems.
A complete management system for PV systems consists of:
 |
An RCS-PV unit in the field. This unit must be connected to an E-meter that
measures the yield of the PV system. It must also have a connection to an
analogue telephone line. The telephone line can be shared with another user. The
RCS-PV requires a mains outlet for the adapter that powers it. |
 |
A PC with the RCS software and a modem that is connected to a telephone line. |
The software will generally be programmed to call the RCS-PV units at night.
After reading the data from the unit(s), the software automatically processes
the data. Part of the data processing is a check on the yield. If the yield is
below expectation, a message can be faxed or e-mailed. Reports can be send each
day, week or month, depending on the demands of the user.
Technical specifications RCS-PV
Inputs (total 5):
- maximum voltage: 5.4 V
- minimal pulse duration: 10 ms
- maximum resistance pulse contact: 1 kOhm
- maximum frequency: 20 Hz
- suited for opto couplers, switch contact
Outputs (total 8):
- type: open collector (opto coupler)
- maximum voltage: 30 V
- maximum current: 10 mA
Telephone/modem connection:
- type: analogue
- baud rate: 2400 baud

Housing:
- type: DIN rail montage
- dimensions: 93 (b) x 100 (d) x 96 (h)mm
Power supply:
- voltage: 8...12 VDC
- current: 350 mA max.
Ordering information:
Description:
Ordering reference:
RCS-PV
RCS-PV
complete with mains adapter
software and manual on CD
mains adapter for RCS
MA230
(230 VAC)
|