PIB-IV
PRO-NET Home Products Contact

Overview
Datasheets
Download

Description

This board is a universal interface between the PRO-NET network and external equipment. See the overview for a recent list of equipment that can be connected this way.

The board has 2 optically isolated RS-485 interfaces. Devices with an RS-232 interface are connected through an RS-485 to RS-232 converter. Devices with an M-bus interface, are connected through an M-bus power supply and converter.

The PIB-IV interface obtains information from the external equipment and makes it available to the measuring program in PRO-NET. The information from the external equipment can be processed just as if it came from a PRO-NET measuring channel.

Specifications

width

4 TE

power supply

+15VDC,  < 115mA

temperature operating

-10...+50°C

temperature storage

-20...+70°C

jumpers

PRO-NET baud rate, external baud rate, number of stations in PRO-NET, station number

implemented devices

see the overview

Connections

pin

signal

address jumpers

1

0V

2

-15Vdc

3

+15Vdc

4

network +

5

network 0

6

network -

7

0V

8

option jumpers

9

RS-485 A +

10

RS-485 0

11

RS-485 A -

12

RS-485 0

13

RS-485 B +

14

RS-485 0

15

RS-485 B -

16

 

Please contact us if you have any questions or remarks about this website.